2 | PD-SERIES CIRCUIT BREAKER - GENERAL SPECIfiCATIONS
Electrical Tables
VOLTAGE
CURRENT RATING
TableA: ListsULRecognized&CSACertifiedconfigurationsand
performance capabilities as a Component Supplementary Protector.
PD-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTOR & EARTH LEAKAGE CURRENT INTERRUPTER
INTERRUPTING LEAKAGE
CAPACITY (AMPS) CURRENT
Table B: Lists TUV Certified configurations and performance capabilities
as a Circuit breaker incorporating residual current protection.
FULL
GENERAL
UL / CSA
MUST - TRIP
CIRCUIT
MAX RATING
FREQUENCY
LOAD
PURPOSE
WITHOUT
RATING
CONFIGURATION
SERIES
VOLTS
120/208
120/208
208-240
480Y
HERTZ
50/60
50/60
50/60
50/60
PHASE
1
3 1
3
3
AMPS
1-50
1-50
1-50
1-30
AMPS
---
---
---
30.1-50
BACKUP FUSE
5000
5000
2000
2000
(MILLIAMPS)
7-100
7-100
7-100
7-100
Breaker)
Ampere Rating
Electrical
Maximum Voltage AC , 480 WYE/277 VAC, 50/60 Hz
Standard Current Ratings 1.00, 2.50, 5.00, 7.50, 10.0, 15.0,
20.0, 25.0, 30.0, 35.0, 40.0 & 50.0
amps. For other ratings, consult factory.
Insulation Resistance Minimum of 100 Megohms @ 500 VDC.
Dielectric Strength 1960 VAC, 60 Hz for one minute
between all electrically isolated
terminals.
Resistance, Impedance from Line to Load Terminal
(Values Based on Series Trip Circuit
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
Mechanical
Endurance
Trip Free
Trip Indication
Physical
10,000 ON-OFF operations @ 6 per
minute; with rated current and voltage.
All SmartGuard equipment leakeage
circuit breakers will trip on overload
or leakage to ground, even when
actuator is forcibly held in the ON
position.
The actuator moves to the OFF
position when an overload or earth
leakage ground fault causes the
breaker to trip. The LED is illuminated
when leakage to ground causes the
circuit breaker to trip.
Inrush Pulse Tolerance
12x
4.165
20.1 - 50.0
Pulse Tolerance Curve
60 Hz 1/2 Cycle
I r
Time Delay Curves
22, 24, 26
t
8.33 16.67
Time in
Milliseconds
Leakage To Ground
Standard Must Trip
Leakage Current Ratings 7, 10, 15, 30, 50 & 100 milliamps. For
other ratings, consult factory.
Trip Time 300 ms Max. @ 100%, 40ms Max. @
500% of must trip leakage current.
Test Button On breaker face above actuator.
Leakage Trip Indicator Red LED on breaker face above
actuator.
Number of Poles 2, 3 & 4
Length (included switched
or unswitched neutral) 4.2 inches ( 106.7 mm)
Width 2-pole: 3.0 inches (76.2 mm)
3-pole: 3.75 inches (95.3 mm)
4-pole: 4.5 inches (114.3 mm)
Depth 2.5inches (63.5mm).
Weight: 2-pole 16.0 oz. (453.6 gm)
3-pole: 21.4 oz. (606.7 gm)
4-pole: 26.9 oz. (762.6 gm)
Standard Colors Housing - gray;
Actuator - black, red, or white
Mounting Front Panel or Standard 35mm
Symmetrical DIN Rail (35 x 7.5 or
35 x 15mm per DIN EN5002).
Termination Box Lug
Environmental
Operating Temperature +10°C to +50°C
*Manufacturer reserves the right to change product specification without prior notice.
60 JOHNSON AVENUE ? PLAINVILLE, CT 06062–1177 ? PHONE: (860) 793–9281 ? FAX: (860) 793–9231
EMAIL: SALES @ CARLINGTECH.COM ? WWW.CARLINGTECH.COM
相关PDF资料
PFMF.260.2 PFMF PTC FUSE SMT 2.6A 1812
PFNF.200.2 PFNF PTC FUSE SMT 2A 1206
PFRY.375 PTC-FUSE RADIAL 72 VDC
PFSM.150.33.2 FUSE PTC 8A 15V FST-TRIP SMD
PFUF.150.2 FUSE PTC 3A 6V RESET SMD
PG103001 KIT PROGRAMMERS MICROID
PG164101 PROGRAMMER BASELINE FLASH MCU
PGD050S030CSF01 SUPPRESSOR ESD ARRAY 50PIN DSUB
相关代理商/技术参数
PDA-B-24-620-B-2A1-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk
PDA-B-24-620-B-2AB-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk
PDA-B-24-620-C-1AA-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk
PDA-B-24-620-C-1AD-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk
PDA-B-24-620-D-1A2-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk
PDA-B-24-620-D-1AD-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk
PDA-B-24-620-E-1AA-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk
PDA-B-24-620-E-1AD-1-C 制造商:Carling Technologies 功能描述:PDC-SERIES (SMART-GUARD) BKR - Bulk